Application |
Medium temperature [°C] | -25…110 |
Electrical data |
Operating voltage [V] | 10…30 DC |
Current consumption [mA] | < 22 |
Protection class | III |
Reverse polarity protection | yes |
Outputs |
Electrical design | PNP |
Output function | normally open |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | 200 |
Switching frequency DC [Hz] | 40 |
Short-circuit protection | yes |
Overload protection | yes |
Detection zone |
Sensing range [mm] | 0.5…24 |
Sensing range adjustable | yes |
Factory setting sensing range [mm] | 15 |
Real sensing range Sr [mm] | 15 ± 10 % |
Accuracy / deviations |
Hysteresis [% of Sr] | 1…15 |
Switch point drift [% of Sr] | -15…15 |
Interfaces |
Communication interface | IO-Link |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 |
Profiles | Smart Sensor: Process Data Variable; Device Identification |
SIO mode | yes |
Required master port type | A |
Min. process cycle time [ms] | 20 |
Operating conditions |
Ambient temperature [°C] | -25…80 |
Protection | IP 65; IP 67; IP 69K |
Tests / approvals |
EMC | EN 61000-4-2 | 30 kV AD / 4 kV CD | EN 61000-4-3 | 10 V/m | EN 61000-4-4 | 2 kV | EN 61000-4-6 | 10 V | EN 55011 | class B | |
Vibration resistance | DIN EN 60947-5-2 | 1 mm amplitude, oscillation period 5 min., 30 min. per axis at resonance or 55 Hz | |
Shock resistance | DIN EN 60947-5-2 | 30 g 6 shocks / 11 ms half-sine (x, y, z) | |
MTTF [years] | 903.84 |
UL approval | |
Mechanical data |
Weight [g] | 54.2 |
Housing | threaded type |
Mounting | quasi flush |
Dimensions [mm] | M30 x 1.5 / L = 92 |
Thread designation | M30 x 1.5 |
Materials | PBT; PC; POM |
Tightening torque [Nm] | 8 |
Displays / operating elements |
Display | switching status | 1 x LED, yellow | |
Accessories |
Accessories (supplied) | |
Remarks |
Pack quantity | 1 pcs. |
Electrical connection – plug |
Connection | Connector: 1 x M12 |
评价
目前还没有评价