Application |
Pressure rating [bar] | one hundred |
Note on pressure rating | |
Electrical data |
Operating voltage [V] | 10 … 36 DC |
Current consumption [mA] | <25 |
Protection class | III |
Reverse polarity protection | yes |
Outputs |
Electrical design | PNP |
Output function | normally open |
Max. voltage drop switching output DC [V] | 2.5 |
Permanent current rating of switching output DC [mA] | one hundred |
Switching frequency DC [Hz] | 250 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Detection zone |
Sensing range [mm] | 25 |
Real sensing range Sr [mm] | 25 ± 10% |
Operating distance [mm] | 0 … 20.3 |
Increased sensing range | yes |
Accuracy / deviations |
Correction factor | steel: 1 / stainless steel: 1 / brass: 0.7 / aluminum: 0.6 / copper: 0.4 |
Hysteresis [% of Sr] | 1 … 20 |
Switch point drift [% of Sr] | -10 … 10 |
Operating conditions |
Ambient temperature [° C] | 0 … 100 |
Protection | IP 65; IP 67; IP 68; IP 69K |
Tests / approvals |
EMC | EN 61000-4-2 ESD | 4 kV CD / 8 kV AD | EN 61000-4-3 HF radiated | 10 V / m | EN 61000-4-4 Burst | 2 kV | EN 61000-4-6 HF conducted | 10V | EN 55011 emission | class B | |
Impact resistance | |
MTTF [years] | 740 |
UL approval | TA | 0 … 40 ° C | Enclosure type | Type 1 | voltage supply | Limited Voltage / Current | File number UL | E174191 | |
Mechanical data |
Weight [g] | 133.5 |
Housing | threaded type |
Mounting | non-flush mountable |
Dimensions [mm] | M30 x 1.5 / L = 70 |
Thread designation | M30 x 1.5 |
Materials | housing: stainless steel (1.4404 / 316L); sensing face: stainless steel (1.4404 / 316L); lock nuts: stainless steel (1.4404 / 316L) |
Full-metal housing | yes |
Displays / operating elements |
Display | switching status | 4 x 90 ° LED, yellow | |
Accessories |
Accessories (supplied) | |
Remarks |
Pack quantity | 1 pcs. |
Electrical connection – plug |
Connection | Connector: 1 x M12; Contacts: gold-plated |
评价