Application |
Application | vibration monitor to DIN ISO 10816 |
Electrical data |
Operating voltage [V] | 18…32 DC |
Current consumption [mA] | < 50 |
Protection class | III |
Inputs / outputs |
Total number of inputs and outputs | 2 |
Number of inputs and outputs | Number of digital outputs: 1; Number of analogue outputs: 1 |
Outputs |
Output signal | switching signal; analogue signal |
Number of digital outputs | 1 |
Output function | normally closed |
Max. voltage drop switching output DC [V] | 2 |
Permanent current rating of switching output DC [mA] | 500 |
Number of analogue outputs | 1 |
Analogue current output [mA] | 4…20 |
Max. load [Ω] | 500 |
Short-circuit protection | yes |
Type of short-circuit protection | pulsed |
Overload protection | yes |
Measuring/setting range |
Measuring range of vibration [mm/s] | 0…25; (RMS) |
Frequency range [Hz] | 10…1000 |
Number of measurement axes | 1 |
Accuracy / deviations |
Measuring error [% of the final value] | < ± 3 |
Switch point accuracy | < ±4; (% of the final value) |
Repeatability | < 0,5; (% of the final value) |
Linearity deviation | 0,25 % |
Operating conditions |
Ambient temperature [°C] | -25…80 |
Note on ambient temperature | |
Protection | IP 67 |
Tests / approvals |
EMC | EN 61000-4-2 ESD | 4 kV CD / 8 kV AD | EN 61000-4-3 HF radiated | 10 V/m | EN 61000-4-4 Burst | 2 kV | EN 61000-4-6 HF conducted | 10 V | |
Shock resistance | |
MTTF [years] | 510 |
Mechanical data |
Weight [g] | 114 |
Type of mounting | M8 x 1,25 |
Materials | PBT; PC; FKM; stainless steel (1.4404 / 316L) |
Tightening torque [Nm] | 15 |
Sensor type | microelectromechanical system (MEMS) |
Displays / operating elements |
Display | operation | LED, green | switching status | LED, yellow | |
With scale | yes |
Operating elements | setting ring | setting ring | |
Remarks |
Pack quantity | 1 pcs. |
Electrical connection |
Connection | Connector: 1 x M12 |
Reviews