IFM-PM1604

  • Description
  • Reviews (0)

Description

Application
Measuring element ceramic-capacitive pressure measuring cell
Application hygienic systems
Media viscous media and liquids with suspended particles; liquids and gases
Medium temperature [°C] -25…125; (150 max. 1h)
Pressure rating
50 bar 725 psi 5 MPa
Min. bursting pressure
150 bar 2175 psi 15 MPa
Vacuum resistance [mbar] -1000
Type of pressure relative pressure
No dead space yes
MAWP (for applications according to CRN) [bar] 50
Electrical data
Operating voltage [V] 18…30 DC
Min. insulation resistance [MΩ] 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Integrated watchdog yes
2-wire
Current consumption [mA] 3.5…21.5
Power-on delay time [s] 1
3-wire
Current consumption [mA] < 45
Power-on delay time [s] 0.5
Inputs / outputs
Number of inputs and outputs Number of analogue outputs: 1
Outputs
Total number of outputs 1
Output signal analogue signal
Number of analogue outputs 1
Analogue current output [mA] 4…20; (scalable)
Max. load [Ω] 700; (Ub = 24 V; (Ub – 9 V) / 21.5 mA)
Short-circuit proof yes
Overload protection yes
Measuring/setting range
Measuring range
-1…10 bar -14.5…145 psi -0.1…1 MPa
Analogue start point
-1…8 bar -14.5…116 psi -0.1…0.8 MPa
Analogue end point
1…10 bar 14.5…145 psi 0.1…1 MPa
In steps of
0.005 bar 0.1 psi 0.0005 MPa
Factory setting
ASP = 0.0 bar AEP = 10.0 bar
Accuracy / deviations
Repeatability [% of the span] < ± 0,1; (with temperature fluctuations < 10 K; Turn down 1:1)
Characteristics deviation [% of the span] < ± 0,2 (nach DIN EN 61298-2); (incl. drift when overtightened, zero point and span error, non-linearity, hysteresis; Turn down 1:1)
Linearity deviation [% of the span] < ± 0,15; (Turn down 1:1)
Hysteresis deviation [% of the span] < ± 0,15; (Turn down 1:1)
Long-term stability [% of the span] < ± 0,1; (Turn down 1:1; per year)
Temperature coefficient zero point [% of the span / 10 K] < ± 0,05; (0…70 °C)
Temperature coefficient span [% of the span / 10 K] < ± 0,15; (0…70 °C)
Response times
Damping for the analogue output dAA [s] 0…4
2-wire
Step response time analogue output [ms] 30
3-wire
Step response time analogue output [ms] 7
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
IO-Link device ID 662 d / 00 02 96 h
Profiles Digital Measuring Sensor (0x000A), Identification and Diagnosis (0x4000)
SIO mode no
Required master port type A
Process data analogue 3
Min. process cycle time [ms] 3.2
Operating conditions
Ambient temperature [°C] -25…80
Storage temperature [°C] -40…100
Protection IP 67; IP 68; IP 69K
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance
DIN EN 60068-2-27 50 g (11 ms)
Vibration resistance
DIN EN 60068-2-6 20 g (10…2000 Hz)
MTTF [years] 323
UL approval
UL Approval no. J022
Mechanical data
Weight [g] 302
Materials stainless steel (1.4404 / 316L); PBT
Materials (wetted parts) ceramics (99.9 % Al2O3); PTFE; stainless steel (1.4435 / 316L); surface characteristics: Ra < 0,4 / Rz 4
Min. pressure cycles 100 million
Tightening torque [Nm] 20; (recommended tightening torque depends on lubrication, seal and pressure rating)
Process connection threaded connection G 1 external thread sealing cone
Displays / operating elements
Display unit bar; psi; MPa
Remarks
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; Contacts: gold-plated

Reviews

There are no reviews yet.


Be the first to review “IFM-PM1604”

ENQUIRY