Application
Measuring element ceramic-capacitive pressure measuring cell
Media liquids and gases
Medium temperature [°C] -25…80
Pressure rating
75 bar 1087 psi 7.5 MPa
Min. bursting pressure
150 bar 2175 psi 15 MPa
Vacuum resistance [mbar] -1000
Type of pressure relative pressure
Electrical data
Operating voltage [V] 18…30 DC; (according to EN 50178 SELV/PELV)
Current consumption [mA] < 35
Min. insulation resistance [MΩ] 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Power-on delay time [s] 0.3
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 1; Number of analogue outputs: 1
Outputs
Total number of outputs 2
Output signal switching signal; analogue signal; IO-Link; (configurable)
Electrical design PNP
Number of digital outputs 1
Output function normally open / normally closed; (parameterisable)
Max. voltage drop switching output DC [V] 2.5
Permanent current rating of switching output DC [mA] 150; (200 (…60 °C) 250 (…40 °C))
Switching frequency DC [Hz] < 170
Number of analogue outputs 1
Analogue current output [mA] 4…20; (0 bar = 4 mA; 10 bar = 20 mA)
Max. load [Ω] 500
Analogue voltage output [V] 0…10; (0 bar = 0 V; 10 bar = 10 V)
Min. load resistance [Ω] 2000
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Measuring range
-1…10 bar -14.5…145 psi -100…1000 kPa -0.1…1 MPa
Set point SP
-0.9…10 bar -13.5…145 psi -0.09…1 MPa
Reset point rP
-0.95…9.95 bar -14…144.5 psi > -0.095 MPa
In steps of
0.05 bar 0.5 psi 0.005 MPa
Accuracy / deviations
Switch point accuracy [% of the span] < ± 0,5
Repeatability [% of the span] < ± 0,1; (with temperature fluctuations < 10 K)
Characteristics deviation [% of the span] < ± 0,25 (BFSL) / < ± 0,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting)
Hysteresis deviation [% of the span] < ± 0,25
Long-term stability [% of the span] < ± 0,05; (per 6 months)
Temperature coefficient zero point [% of the span / 10 K] < ± 0,2; (-0…80 °C)
Temperature coefficient span [% of the span / 10 K] < ± 0,2; (-0…80 °C)
Response times
Response time [ms] < 3
Delay time programmable dS, dr [s] 0…50
Damping for the switching output dAP [s] 0…4
Damping for the analogue output dAA [s] 0…4
Max. response time analogue output [ms] 3
Software / programming
Parameter setting options hysteresis / window; normally open / normally closed; switch-on/switch-off delay; Damping; Display unit; current/voltage output
Interfaces
Communication interface IO-Link
Transmission type COM2
IO-Link revision 1.1
SDCI standard IEC 61131-9
IO-Link device ID 431 d / 00 01 af h
Profiles Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO mode yes
Required master port type A
Process data analogue 1
Process data binary 1
Min. process cycle time [ms] 2.3
Operating conditions
Ambient temperature [°C] -25…80
Storage temperature [°C] -40…100
Protection IP 65; IP 67
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance
DIN EN 60068-2-27 50 g (11 ms)
Vibration resistance
DIN EN 60068-2-6 20 g (10…2000 Hz)
MTTF [years] 226
UL approval
UL Approval no. J004
Pressure Equipment Directive Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight [g] 281.5
Materials stainless steel (1.4404 / 316L); PBT+PC-GF30; PBT-GF20; PC
Materials (wetted parts) stainless steel (1.4404 / 316L); Al2O3 (ceramics); FKM
Min. pressure cycles 100 million
Tightening torque [Nm] 25…35; (recommended tightening torque; depends on lubrication, seal and pressure rating)
Process connection threaded connection G 1/4 external thread (DIN EN ISO 1179-2); internal threadM5
Process connection sealing FKM (to DIN 3869)
Restrictor element integrated no (can be retrofitted)
Displays / operating elements
Display
Display unit 3 x LED, green (bar, psi, MPa)
switching status 1 x LED, yellow
measured values alphanumeric display, red/green 4-digit
Remarks
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12; Contacts: gold-plated