IFM-PK5522

IFM-PK5522

  • Simple switch point setting via setting ring
  • Stainless steel measuring cell, e.g. for freons in refrigerating technology
  • Mechanical locking prevents inadvertent switch point manipulation
  • High bursting pressure
  • For use in hydraulic and pneumatic applications
ENQUIRY DATASHEET
  • Description
  • Reviews (0)

Description

Application
Media liquids and gases
Medium temperature [°C] -25…80
Pressure rating
200 bar 2900 psi
Min. bursting pressure
1000 bar 14500 psi
Type of pressure relative pressure
Electrical data
Operating voltage [V] 9.6…32 DC
Current consumption [mA] < 25
Min. insulation resistance [MΩ] 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 1
Outputs
Total number of outputs 1
Output signal switching signal
Electrical design PNP
Number of digital outputs 1
Output function normally open
Max. voltage drop switching output DC [V] 2
Permanent current rating of switching output DC [mA] 500
Switching frequency DC [Hz] 100
Short-circuit protection yes
Type of short-circuit protection pulsed
Overload protection yes
Measuring/setting range
Measuring range
0…100 bar 0…1450 psi
Set point SP
3…100 bar 44…1450 psi
Hysteresis
2 bar 29 psi
Accuracy / deviations
Switch point accuracy [% of the final value] < ± 2,5; (Setting accuracy)
Repeatability [% of the final value] < ± 0,5; (with temperature fluctuations < 10 K)
Characteristics deviation [% of the final value] < ± 1,5 (BFSL) / < ± 2,5 (LS); (BFSL = Best Fit Straight Line; LS = limit value setting)
Temperature drift per 10 K < ± 0.5
Software / programming
Adjustment of the switch point setting ring
Operating conditions
Ambient temperature [°C] -25…80
Storage temperature [°C] -40…100
Protection IP 67
Tests / approvals
EMC
EN 61000-4-2 ESD 4 kV CD / 8 kV AD
EN 61000-4-3 HF radiated 10 V/m
EN 61000-4-4 Burst 2 kV
EN 61000-4-6 HF conducted 10 V
Shock resistance
DIN IEC 68-2-27 50 g (11 ms)
Vibration resistance
DIN IEC 68-2-6 20 g (10…2000 Hz)
MTTF [years] 1030
Pressure Equipment Directive Sound engineering practice; can be used for group 2 fluids; group 1 fluids on request
Mechanical data
Weight [g] 94
Materials PBT; PC; FKM; stainless steel (1.4404 / 316L)
Materials (wetted parts) stainless steel (1.4404 / 316L); FKM
Min. pressure cycles 50 million
Tightening torque [Nm] 25
Process connection threaded connection G 1/4 external thread internal threadM5
Restrictor element integrated no (can be retrofitted)
Displays / operating elements
Display
operation LED, green
switching status LED, yellow
With scale yes
Remarks
Pack quantity 1 pcs.
Electrical connection
Connection Connector: 1 x M12

Reviews

There are no reviews yet.


Be the first to review “IFM-PK5522”

ENQUIRY







    X
    ENQUIRY