Electrical data |
Operating voltage [V] | 18…30 DC; (“supply class 2” to cULus) |
Current consumption [mA] | 50 |
Sensor supply US |
Current rating per port [A] | 0.1 |
Inputs / outputs |
Number of inputs and outputs | Number of digital inputs: 8 |
Inputs |
Number of digital inputs | 8; (4 x 2) |
Input circuit of digital inputs | PNP |
Input current limitation [mA] | 15 |
Input current High [mA] | 6…10 |
Input current Low [mA] | 0…2 |
Min. switching level high signal [V] | 11 |
Digital inputs protected against short circuits | yes |
Interfaces |
Communication interface | IO-Link |
IO-Link Device |
Transmission type | COM2 (38,4 kBaud) |
IO-Link revision | 1.1 |
SDCI standard | IEC 61131-9 |
IO-Link device ID | 0x000316 |
SIO mode | no |
Process data binary | 32 |
Min. process cycle time [ms] | 2.9 |
Operating conditions |
Ambient temperature [°C] | -25…70 |
Storage temperature [°C] | -25…85 |
Max. relative air humidity [%] | 90; (non condensing) |
Protection | IP 67 |
Tests / approvals |
EMC | EN 61000-6-2 | | EN 61000-6-3 | | IEC 61131-9 | | |
Mechanical data |
Weight [g] | 144.5 |
Materials | PBT; socket: brass nickel-plated; O-ring: FKM |
Displays / operating elements |
Display | operation | LED, green | errors | LED, red | function | LED, yellow | |
Accessories |
Accessories (supplied) | panel for labelling | Protective caps: 2 | |
Accessories (optional) | Protective cap: M8, E73005 | |
Remarks |
Remarks | For use in NFPA 79 applications only | The device is to be operated to IO-Link specification V1.1.2. | The maximum cable length of the IO-Link cable is 20 m. | |
Pack quantity | 1 pcs. |
Electrical connection – Process connection |
| Connector: M8 |
Electrical connection – IO-Link |
| Connector: M12 |