IFM-AL1900

IFM-AL1900

  • Separation between automation network and IT network
  • For connection of up to eight IO-Link devices
  • Reliable transmission of machine data, process parameters and diagnostic data to the controller
  • With PROFINET interface and separate TCP/IP JSON interface
  • Small design requiring only very little space for control panel mounting

 

ENQUIRY DATASHEET
  • Description
  • Reviews (0)

Description

Application
Application I/O modules for use in the control cabinet
Electrical data
Operating voltage [V] 20…30 DC; (US; to SELV/PELV)
Current consumption [mA] 300…3900; (US)
Protection class III
Sensor supply US
Max. current load total [A] 3.6
Inputs / outputs
Total number of inputs and outputs 16; (configurable)
Number of inputs and outputs Number of digital inputs: 8; Number of digital outputs: 8
Inputs
Number of digital inputs 8; (IO-Link Port Class A)
Switching level high [V] 11…30
Switching level low [V] 0…5
Digital inputs protected against short circuits yes
Outputs
Number of digital outputs 8; (IO-Link Port Class A)
Max. current load per output [mA] 200
Short-circuit proof yes
Interfaces
Communication interface Ethernet; IO-Link
Ethernet – Internet of Things
Transmission standard 10Base-T; 100Base-TX
Transmission rate 10; 100
Protocol TCP/IP JSON
Factory settings
IP address: 169.254.x.x
subnet mask: 255.255.0.0
gateway IP address: 0.0.0.0
MAC address: see type label
Ethernet – PROFINET
Transmission standard 10Base-T; 100Base-TX
Transmission rate 10; 100
Protocol PROFINET IO
Factory settings
IP address: 0.0.0.0
subnet mask: 0.0.0.0
gateway IP address: 0.0.0.0
MAC address: see type label
IO-Link Master
Transmission type COM 1 / COM 2 / COM 3
IO-Link revision 1.1
Number of ports class A 8
Operating conditions
Ambient temperature [°C] -25…65
Storage temperature [°C] -25…85
Max. relative air humidity [%] 90
Protection IP 20
Tests / approvals
EMC
EN 61000-6-2
EN 61000-6-4
MTTF [years] 90
Mechanical data
Weight [g] 330
Materials housing: PA
Accessories
Accessories (supplied)
COMBICON connectors: 9
Remarks
Remarks
For further information please see the operating instructions.

Reviews

There are no reviews yet.


Be the first to review “IFM-AL1900”

ENQUIRY







    X
    ENQUIRY